收藏 分享(赏)

ASTM_E_2257_-_13a.pdf

上传人:益****师 文档编号:169418 上传时间:2023-03-04 格式:PDF 页数:20 大小:585.40KB
下载 相关 举报
ASTM_E_2257_-_13a.pdf_第1页
第1页 / 共20页
ASTM_E_2257_-_13a.pdf_第2页
第2页 / 共20页
ASTM_E_2257_-_13a.pdf_第3页
第3页 / 共20页
ASTM_E_2257_-_13a.pdf_第4页
第4页 / 共20页
ASTM_E_2257_-_13a.pdf_第5页
第5页 / 共20页
ASTM_E_2257_-_13a.pdf_第6页
第6页 / 共20页
亲,该文档总共20页,到这儿已超出免费预览范围,如果喜欢就下载吧!
资源描述

1、Designation:E225713aAn American National StandardStandard Test Method forRoom Fire Test of Wall and Ceiling Materials andAssemblies1This standard is issued under the fixed designation E2257;the number immediately following the designation indicates the year oforiginal adoption or,in the case of revi

2、sion,the year of last revision.A number in parentheses indicates the year of last reapproval.Asuperscript epsilon()indicates an editorial change since the last revision or reapproval.1.Scope1.1 This is a fire-test-response standard.1.2 This test method is intended to evaluate,under specifiedfire-exp

3、osure conditions,the contribution to room fire growthprovided by wall or ceiling materials and assemblies,or both.The method is not intended to evaluate the fire endurance ofassemblies or fires originating in the wall assembly.Themethod provides a means to evaluate the effectiveness ofthermal barrie

4、rs in restricting the contribution of combustiblematerials in the wall assembly to fire growth in a room fire.1.3 This test method,simulating a fire in the corner of a2420 by 3630 mm(8 by 12 ft)room containing a single opendoorway,provides a means to evaluate the relative perfor-mance of specified w

5、all and ceiling materials or assemblieswhen they are used together in the same relationship within anenclosure,and simulating the manner in which they will beused.1.4 This test method is intended to evaluate the contributionto fire growth provided by a surface product using a specifiedignition sourc

6、e.It shall,however,be noted that the type,position and heat output of the ignition source will consider-ably influence fire growth.The thermal exposure conditionsfrom the ignition source specified in this method will result inflashover during the 20 min duration for many common finishmaterials,in pa

7、rticular if specimens are mounted on the wallsand the ceiling(standard configuration).1.5 This test method provides a means for evaluating walland ceiling finish materials and assemblies,including panels,tiles,boards,sprayed or brushed coatings,etc.This test methodis not intended to evaluate floorin

8、g materials or furnishings.1.6 This method shall be used in conjunction with GuideE603,which covers instrumentation and the general effect ofvarious parameters,and Guide E2067,which deals withfull-scale oxygen consumption calorimetry.1.7 The values stated in SI units are to be regarded as thestandar

9、d.The units given in parentheses are for informationonly.1.8 The text of this standard references notes and footnoteswhich provide explanatory information.These notes and foot-notes(excluding those in figures)shall not be considered asrequirements of the standard.1.9 This standard is used to measure

10、 and describe theresponse of materials,products,or assemblies to heat and flameunder controlled conditions,but does not by itself incorporateall factors required for fire-hazard or fire-risk assessment of thematerials,products,or assemblies under actual fire conditions.1.10 This standard does not pu

11、rport to address all of thesafety concerns,if any,associated with its use.It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.11 Fire testing is inherently hazardous.Adequ

12、ate safe-guards for personnel and property shall be employed inconducting these tests.2.Referenced Documents2.1 ASTM Standards:2E84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE136 Test Method for Behavior of Materials in a VerticalTube Furnace at 750CE176 Terminology of Fire

13、 StandardsE603 Guide for Room Fire ExperimentsE2067 Practice for Full-Scale Oxygen Consumption Calo-rimetry Fire Tests2.2 ISO Standards:ISO 9705 Fire TestsReaction to FireRoom Fire Test3ISO 13943 Fire SafetyVocabulary31This test method is under the jurisdiction of ASTM Committee E05 on FireStandards

14、 and is the direct responsibility of Subcommittee E05.21 on Smoke andCombustion Products.Current edition approved Aug.1,2013.Published September 2013.Originallyapproved in 2003.Last previous edition approved in 2013 as E2257-13.DOI:10.1520/E2257-13A.2For referenced ASTM standards,visit the ASTM webs

15、ite,www.astm.org,orcontact ASTM Customer Service at serviceastm.org.For Annual Book of ASTMStandards volume information,refer to the standards Document Summary page onthe ASTM website.3Available from International Organization for Standardization(ISO),1 rue deVaremb,Case postale 56,CH-1211,Geneva 20

16、,Switzerland.Copyright ASTM International,100 Barr Harbor Drive,PO Box C700,West Conshohocken,PA 19428-2959.United States1 2.3 NFPA Standards:NFPA 265 Standard Method of Tests for Evaluating RoomFire Growth Contribution of Textile Wall Coverings4NFPA 286 Standard Method of Tests for Evaluating Contri-bution of Wall and Ceiling Interior Finish to Room FireGrowth43.Terminology3.1 DefinitionsFor definitions of terms used in thisstandard,see Terminology E176 and ISO 13943.In case ofconflict,the defi

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 专业资料 > 国外标准

copyright@ 2008-2023 wnwk.com网站版权所有

经营许可证编号:浙ICP备2024059924号-2