收藏 分享(赏)

ASTM_G_165_-_99_2017.pdf

上传人:益****师 文档编号:190143 上传时间:2023-03-04 格式:PDF 页数:5 大小:202.08KB
下载 相关 举报
ASTM_G_165_-_99_2017.pdf_第1页
第1页 / 共5页
ASTM_G_165_-_99_2017.pdf_第2页
第2页 / 共5页
ASTM_G_165_-_99_2017.pdf_第3页
第3页 / 共5页
ASTM_G_165_-_99_2017.pdf_第4页
第4页 / 共5页
ASTM_G_165_-_99_2017.pdf_第5页
第5页 / 共5页
亲,该文档总共5页,全部预览完了,如果喜欢就下载吧!
资源描述

1、Designation:G16599(Reapproved 2017)Standard Practice forDetermining Rail-to-Earth Resistance1This standard is issued under the fixed designation G165;the number immediately following the designation indicates the year oforiginal adoption or,in the case of revision,the year of last revision.A number

2、in parentheses indicates the year of last reapproval.Asuperscript epsilon()indicates an editorial change since the last revision or reapproval.1.Scope1.1 This practice covers the procedures necessary to followfor measuring resistance-to-earth of the running rails which areused as the conductors for

3、returning the train operating currentto the substation in electric mass transit systems.1.2 The values stated in SI units are to be regarded as thestandard.The values given in parentheses are for informationonly.1.3 This standard does not purport to address all of thesafety concerns,if any,associate

4、d with its use.It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.4 This international standard was developed in accor-dance with internationally recognized principles on

5、 standard-ization established in the Decision on Principles for theDevelopment of International Standards,Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade(TBT)Committee.2.Referenced Documents2.1 ASTM Standards:2G15 Terminology Relating to Corrosion and Co

6、rrosion Test-ing(Withdrawn 2010)33.Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 cross bondinsulated copper cables that connectedbetween adjacent sections of track to ensure electrical conti-nuity between them.3.1.2 direct fixation fastenera device for fastening runningrails to

7、 their support structures.3.1.3 impedance bonda device connected to running railsfor automatic train operations.3.1.4 The terminology used herein,if not specifically de-fined otherwise,shall be in accordance with Terminology G15.Definitions provided herein,and not given in TerminologyG15,are limited

8、 to this practice.4.Significance and Use4.1 Low resistance between the rails and earth could resultin large magnitudes of stray earth currents with the attendantcorrosion damage to underground metallic structures.4.2 These measurements are of a low voltage type and arenot designed to evaluate the hi

9、gh voltage dielectric character-istics of the rail insulating elements.4.3 Sections of track with rail-to-earth resistances less thanacceptable minimums must be tested in greater detail todetermine the reason(s)for this condition.Determination of thereason(s)for any low rail-to-earth resistance may

10、require theuse of special testing techniques or special instruments,orboth,beyond the scope of this practice.4.4 The electrical tests call for the use of electric meters thathave varying characteristics depending on cost,manufacture,and generic type.It is assumed that any person employing thetest pr

11、ocedures contained herein will know how to determineand apply proper correction factors and that they will havesufficient knowledge to ensure reasonable accuracy in the dataobtained.4.5 This practice does not encompass all possible fieldconditions to obtain rail-to-earth resistance characteristics.N

12、ogeneral set of test procedures will be applicable to all situa-tions.5.Equipment5.1 Indicating dc;high impedance(minimum ten megohm)voltmeter(two required);multi-scale,capable of reading posi-tive and negative values without removing test leads;andcovering at least the following full scale ranges:5

13、.1.1 0 to 10 mV,5.1.2 0 to 100 mV,5.1.3 0 to 1 V,5.1.4 0 to 10 V,and5.1.5 0 to 100 V.1This practice is under the jurisdiction of ASTM Committee G01 on Corrosionof Metals and is the direct responsibility of Subcommittee G01.10 on Corrosion inSoils.Current edition approved May 1,2017.Published May 201

14、7.Originallyapproved in 1999.Last previous edition approved in 2012 as G165 99(2012).DOI:10.1520/G0165-99R17.2For referenced ASTM standards,visit the ASTM website,www.astm.org,orcontact ASTM Customer Service at serviceastm.org.For Annual Book of ASTMStandards volume information,refer to the standard

15、s Document Summary page onthe ASTM website.3The last approved version of this historical standard is referenced onwww.astm.org.Copyright ASTM International,100 Barr Harbor Drive,PO Box C700,West Conshohocken,PA 19428-2959.United StatesThis international standard was developed in accordance with inte

16、rnationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards,Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade(TBT)Committee.1 5.1.6 Meters shall be accurate within 1%of full scale.5.2 Direct current ammeter,multi-scale,covering the fol-lowing full scale ranges:5.2.1 0 to 1 A,5.2.2 0 to 10 A,and5.2.3 0 to 100 A.5.3 Direct current milliammeter,multi-scale,covering thefollowi

展开阅读全文
相关资源
猜你喜欢
相关搜索

当前位置:首页 > 专业资料 > 国外标准

copyright@ 2008-2023 wnwk.com网站版权所有

经营许可证编号:浙ICP备2024059924号-2