资源描述

1、Designation:F96703(Reapproved 2011)Standard Practice forSecurity Engineering Symbols1This standard is issued under the fixed designation F967;the number immediately following the designation indicates the year of originaladoption or,in the case of revision,the year of last revision.Anumber in parent

2、heses indicates the year of last reapproval.Asuperscriptepsilon()indicates an editorial change since the last revision or reapproval.1.Scope1.1 This practice utilizes symbols to depict security systemsand equipment requirements for architectural or engineeringdrawings that are produced either manual

3、ly or by computeraided design(CAD).The symbols depicted include somesymbols that have already been somewhat universally acceptedor that have already been adopted by a standards-writing body,such as by the National Fire Protection Association.1.2 It is not proposed that all of the symbols need to beu

4、tilized since the level of detail required for drawings is likelyto vary.Generic symbols of a class of security device may besufficient in some instances.Moreover,the need to provide ameasure of security in the actual drawing may also suggest aneed to utilize a generic symbol rather than to depict t

5、he exactdevice being installed.1.3 In the event that a greater level of detail is required,it ispossible to combine many of the symbols to create newsymbols that achieve the desired level.While some combina-tions of symbols are shown,it would be impractical to attemptto depict every conceivable comb

6、ination of symbols.It is alsothe intent of this practice that the symbols be capable of beingcontinuously expanded and modified as the industry state of theart changes or as emphasis varies.For example,little attentionis given to document security in the security symbols sincesuch requirements are n

7、ot generally fully met during construc-tion periods but are rather developed and provided for subse-quently.Since much of this equipment is not installed but is“placed,”such as furniture,there is only one symbol proposed(for example,for document shredders).1.4 This standard does not purport to addre

8、ss all of thesafety concerns,if any,associated with its use.It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2.Keywords2.1 computer aided design;security engineering;symb

9、ols1.ANNOTATIONExisting EquipmentPoint and Zone IndicatorConnection Between Devices(for example,button and lock)Detail and Reference DrawingDoor Number(if more than one door in room,use sub-letter)Room or Space NumberDevice Number(reference device schedule)Device ReferenceA=Drawing SheetB=DetailC=De

10、vice Zone Number2.ACCESS CONTROLGeneric Card Reader(reference door schedule orspecifications for type):P=pedestal mountCard Reader with Touch Pad1This practice is under the jurisdiction of ASTM Committee F12 on SecuritySystems and Equipmentand is the direct responsibility of Subcommittee F12.10 onSy

11、stems Products and Services.Current edition approved March 1,2011.Published June 2011.Originallyapproved in 1986.Last previous edition approved in 2003 as F967 03.DOI:10.1520/F0967-03R11.Copyright ASTM International,100 Barr Harbor Drive,PO Box C700,West Conshohocken,PA 19428-2959.United States1 Tok

12、en-Type Access ControlCCTV and Card ReaderCCTV and IntercomSplit Lens CCTV with ID Card ReceptacleApartment Type CCTV with House Phone andTouch Pad(insert“K”“”,as appropriate for key switch)Biometric Access Control Device(reference doorschedule or specifications for type)Touch Pad Lock or Device,Mec

13、hanical orElectronic(reference door schedule for type)Turnstile(reference door schedule for type andfunction)Post and Rail(rope)Generic Screening DeviceX:M=Metal DetectorE=Explosive DetectorX=X-rayT=Tag Detector(EAS)Sally PortIndicating Interlocking DoorsIndicating Space is a“Man-Trap”Card Access Re

14、aderB=BarcodeW=WiegandP=ProximityM=Mag StripeF=Elevator Floor CallH=Elevator Hall CallT=TokenS=Smart CardBiometrics Access Control DeviceH=Hand GeometryF=Finger PrintV=VoiceR=Eye RetinaI=Eye IrisKeypad DeviceCard Reader with KeypadCard Reader with Time and Attendance3.ANNUNCIATION:CONSOLE/PANELStrip

15、(Tallyroll)PrinterPrinterTime Clock with Card ReaderCentral Processing UnitCRT(cathode ray tube/display)Static Map Display(for dynamic map display,use CRT symbol)KeyboardJeweled Signal LightPanel Light Indicator(R=Red,A=Amber,W=White,V=Violet,G=Green,Y=Yellow,B=Blue,O=Orange)Multiplex PanelPanel Sou

16、nd IndicatorPanel Sound and Light IndicatorF967 03(2011)2 ResetPush-Button,Momentary/Make(circuitclosing)Time Delay ModuleControl Device Module,Door ReleaseEnd-of-Line Device ModuleResistance(Ohms)(indicate value;that is,10 000)ThousandsDry Contacts,SetContacts with CurrentPower SwitchField PanelT:C=Card ReaderA=AlarmControl PanelT:B=BurglarF=FireP=PerimeterD=DoorCentral Processing UnitKeyboardPrinterPower SupplyT:L=LockC=CameraP=PanelI=Intercom4.ANNUNCIATION:DEVICESAnnunciation Device,GenericBu