1、Designation:F169709(Reapproved 2015)Standard Specification forPoly(Vinyl Chloride)(PVC)Profile Strip for Machine Spiral-Wound Liner Pipe Rehabilitation of Existing Sewers andConduit1,2This standard is issued under the fixed designation F1697;the number immediately following the designation indicates
2、 the year oforiginal adoption or,in the case of revision,the year of last revision.A number in parentheses indicates the year of last reapproval.Asuperscript epsilon()indicates an editorial change since the last revision or reapproval.1.Scope*1.1 This specification covers requirements and test metho
3、dsfor materials,dimensions,workmanship,stiffness factor,ex-trusion quality,and a form of marking for extruded poly(vinylchloride)(PVC)profile strips used for machine made fieldfabrication of spirally wound pipe liners in the rehabilitation ofa variety of gravity applications such as sanitary sewers,
4、stormsewers,and process piping in diameters of 6 to 180 in.and forsimilar sizes of non-circular pipelines such as arched or ovalshapes and rectangular shapes.1.2 Profile strip produced to this specification is for use infield fabrication of spirally wound liner pipes in nonpressuresewer and conduit
5、rehabilitation,where the spirally woundliner pipe is expanded until it presses against the interiorsurface of the existing sewer or conduit,or,alternatively,wherethe spirally wound liner pipe is inserted as a fixed diameter intothe existing sewer or conduit and the annular space between theliner pip
6、e and the existing sewer or conduit is grouted.1.3 This specification includes extruded profile strips madeonly from materials specified in 5.1.1.4 The values stated in inch-pound units are to be regardedas standard.The values given in parentheses are mathematicalconversions to SI units that are pro
7、vided for information onlyand are not considered standard.1.5 The following precautionary caveat pertains only to thetest method portion,Section 11,of this specification:Thisstandard does not purport to address all of the safety concerns,if any,associated with its use.It is the responsibility of the
8、 userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limita-tions prior to use.2.Referenced Documents2.1 ASTM Standards:3A167 Specification for Stainless and Heat-ResistingChromium-Nickel Steel Plate,Sheet,and Strip(With-drawn 2014)4
9、A176 Specification for Stainless and Heat-Resisting Chro-mium Steel Plate,Sheet,and Strip(Withdrawn 2015)4A653/A653M Specification for Steel Sheet,Zinc-Coated(Galvanized)or Zinc-Iron Alloy-Coated(Galvannealed)by the Hot-Dip ProcessA879/A879M Specification for Steel Sheet,Zinc Coated bythe Electrolyt
10、ic Process for Applications Requiring Des-ignation of the Coating Mass on Each SurfaceA924/A924M Specification for General Requirements forSteel Sheet,Metallic-Coated by the Hot-Dip ProcessD618 Practice for Conditioning Plastics for TestingD790 Test Methods for Flexural Properties of Unreinforcedand
11、 Reinforced Plastics and Electrical Insulating Materi-alsD883 Terminology Relating to PlasticsD1600 Terminology forAbbreviated Terms Relating to Plas-ticsD1784 Specification for Rigid Poly(Vinyl Chloride)(PVC)Compounds and Chlorinated Poly(Vinyl Chloride)(CPVC)CompoundsD2122 Test Method for Determin
12、ing Dimensions of Ther-moplastic Pipe and FittingsD2152 Test Method for Adequacy of Fusion of ExtrudedPoly(Vinyl Chloride)(PVC)Pipe and Molded Fittings byAcetone Immersion1This specification is under the jurisdiction of ASTM Committee F17 on PlasticPiping Systems and is the direct responsibility of
13、Subcommittee F17.67 onTrenchless Plastic Pipeline Technology.Current edition approved March 1,2015.Published April 2015.Originallyapproved in 1996.Last previous edition approved in 2009 as F169709.DOI:10.1520/F1697-09R15.2The rehabilitation of existing pipelines and conduits by the insertion of a sp
14、iralwound liner pipe is covered by patents.(RibLoc Group Limited,Dry Creek,SouthAustralia,Australia and Danby of North America,Inc.,Cary,NC,USA).Interestedparties are invited to submit information regarding the identification of acceptablealternatives to this patented item to the Committee on Standa
15、rds,ASTMHeadquarters,100 Barr Harbor Drive,West Conshohocken,PA 19428-2959.Yourcomments will receive careful consideration at a meeting of the responsibletechnical committee which you may attend.3For referenced ASTM standards,visit the ASTM website,www.astm.org,orcontact ASTM Customer Service at ser
16、viceastm.org.For Annual Book of ASTMStandards volume information,refer to the standards Document Summary page onthe ASTM website.4The last approved version of this historical standard is referenced onwww.astm.org.*A Summary of Changes section appears at the end of this standardCopyright ASTM International,100 Barr Harbor Drive,PO Box C700,West Conshohocken,PA 19428-2959.United States1 F412 Terminology Relating to Plastic Piping SystemsF1741 Practice for Installation of Machine Spiral WoundPoly(V