1、IEC 60947-5-1:2016/COR1:2016 1 IEC 2016 INTERNATIONAL ELECTROTECHNICAL COMMISSION COMMISSION LECTROTECHNIQUE INTERNATIONALE _ IEC 60947-5-1 Edition 4.0 2016-05 Low-voltage switchgear and controlgear Part 5-1:Control circuit devices and switching elements Electromechanical control circuit devices IEC

2、 60947-5-1 dition 4.0 2016-05 Appareillage basse tension Partie 5-1:Appareils et lments de commutation pour circuits de commande Appareils lectromcaniques pour circuits de commande C O R R I G E N D U M 1 5.2.2 Terminal identification and marking Replace the existing text by the following new text:S

3、ubclause 7.1.8.4 of IEC 60947-1:2007 applies,with the additional requirements stated in Annex M.5.2.2 Identification et marquage des bornes Remplacer le texte existant par le nouveau texte suivant:Le Paragraphe 7.1.8.4 de lIEC 60947-1:2007 sapplique,avec les exigences additionnelles identifies dans

4、lAnnexe M.Table 8 Immunity tests Replace the existing table by the following new table:IEC 60947-5-1:2016-05/COR1:2016-07(en-fr)2 IEC 60947-1:2016/COR1:2016 IEC 2016 Table 8 Immunity tests Type of test Basic standard Test level required Acceptance criteria Electrostatic discharge immunity test IEC 6

5、1000-4-2 8 kV/air discharge or 4 kV/contact discharge B k Radiated radio-frequency electromagnetic field immunity test 80 MHz to 1 GHz IEC 61000-4-3 10 V/m A Radiated radio-frequency electromagnetic field immunity test 1,4 GHz to 2 GHz IEC 61000-4-3 3 V/m A Radiated radio-frequency electromagnetic f

6、ield immunity test 2 GHz to 2,7 GHz IEC 61000-4-3 1 V/m A Electrical fast transient/burst immunity test(with capacitive coupling clamp)IEC 61000-4-4 2 kV/5 kHz on power ports a 1 kV/5 kHz on signal ports b B k Surge immunity test(1,2/50 s-8/20 s)c IEC 61000-4-5 2 kV(line to earth)1 kV(line to line)B

7、 Conducted disturbances induced by radiofrequency fields immunity test(150 kHz to 80 MHz)IEC 61000-4-6 10 V A Power frequency magnetic field immunity test d IEC 61000-4-8 30 A/m A Voltage dips immunity test h IEC 61000-4-11 Class 2 e,f 0%during 0,5 cycle Class 3 e,f 0%during 0,5 cycle B k,l Class 2

8、e,f 0%during 1 cycle Class 3 e,f 0%during 1 cycle B Class 2 e,f,g 70%during 25/30 cycles Class 3 e,f,g 40%during 10/12 cycles 70%during 25/30 cycles 80%during 250/300 cycles C Voltage interruptions immunity test h IEC 61000-4-11 Class 2 e,f,g 0%during 250/300 cycles Class 3 e,f,g 0%during 250/300 cy

9、cles C Immunity to harmonics in the supply IEC 61000-4-13 No requirements i a Power port:the point at which a conductor or cable carrying the primary electrical power needed for the operation of the electronic circuit or the switching element or associated equipment is connected.b Signal port:the po

10、int at which a conductor or cable carrying information for transferring data or signals is connected to the electronic circuit or the switching element.c Not applicable for extra-low voltage a.c.ports(30 V)and extra-low voltage d.c.input/output ports(60 V),when the secondary circuits(isolated from t

11、he a.c.mains)are not subject to transient overvoltages.d Applicable only to equipment containing devices susceptible to power frequency magnetic fields.IEC 60947-5-1:2016/COR1:2016 3 IEC 2016 e Class 2 applies to points of common coupling and in-plant points of common coupling in the industrial envi

12、ronment in general.Class 3 applies to in-plant couplings in industrial environment only.This class should be considered when a major part of the load is fed through converters;welding machines are present;large motors are frequently started or loads vary rapidly.The manufacturer shall state the appl

13、icable class.f The given percentage means percentage of the rated operational voltage,e.g.0%means 0 V.g The value before the solidus(/)is for 50 Hz and the value behind is for 60 Hz tests.h Applicable for a.c.equipment only.i Requirements are under study for the future.k For keeping the functionalit

14、y at the system level(e.g.automation or process)the state of the switching element shall not change for more than 1 ms for d.c.devices or one half-cycle of supply frequency for a.c.devices.l For devices with power consumption of more than 750 mW,the recovery time of the switching element may be long

15、er than one half-cycle but shall be less than the maximum recovery time.Tableau 8 Essais dimmunit Remplacer le tableau existant par le nouveau tableau suivant:4 IEC 60947-1:2016/COR1:2016 IEC 2016 Tableau 8 Essais dimmunit Type de lessai Norme de base Niveau dessai exig Critre dacceptation Essai dim

16、munit aux dcharges lectromagntiques IEC 61000-4-2 8 kV/dcharge dans lair ou 4 kV/dcharge au contact B k Essai dimmunit aux champs lectromagntiques rayonns aux frquences radiolectriques 80 MHz 1 GHz IEC 61000-4-3 10 V/m A Essai dimmunit aux champs lectromagntiques rayonns aux frquences radiolectriques 1,4 GHz 2 GHz IEC 61000-4-3 3 V/m A Essai dimmunit aux champs lectromagntiques rayonns aux frquences radiolectriques 2 GHz 2,7 GHz IEC 61000-4-3 1 V/m A Essais dimmunit aux transitoires lectriques r