1、64/1326/CCCOMPILATION OF COMMENTS ON COMMITTEE DRAFTProject number:IEC 60364-5-52,Ed.3.0Reference number of the CD64/1266/CDIEC/TC or SCTC 64Date of circulation2003-08-15Title of the TC or SC:Electrical installations and protection against electric shockTitle of the committee draft:IEC 60364-5-52,Ed
2、.3:Electrical installations of buildings-Part 5-52:Selection and erection ofelectrical equipment-Wiring systemsThe above-mentioned document was distributed to National Committees with a request that comments be submittedComments received see annex 1)DECISION OF THE CHAIRMAN(in cooperation with the s
3、ecretariat)aA revised committee draft will be distributed as a committee draft for vote(CDV)by(date).bA revised committee draft will be distributed for comment by(date)cThe committee draft and comments will be discussed at the next meeting(date)September 2003 Item 6.2.3NOTE In the case of a proposal
4、 a or b made by the chairman,P-members objecting to such a proposal shall inform the Central Officewith copy to the secretary in writing within 2 months of the circulation of this compilation(see ISO/IEC Directives,Part 1,2.5.3).Name or signature of the SecretaryR.PeltaName or signature of the Chair
5、manR.TalonFORM CC(IEC)2002-08-091)to be collated on Form Comments and annexed.2 64/1326/CCAnnexDateDocument2003-08-1564/1266/CDNationalCommitteeClause/SubclauseParagraphFigure/TableType ofcomment(General/Technical/Editorial)COMMENTSProposed changeOBSERVATIONS OF THE SECRETARIATon each comment submit
6、ted1.CACanada supports documentNoted2.CHmethods ofinstallationGeneralThe Swiss National Commitee regrets,that for some“Methods of installation”,the reference method of installation to beused remains still“under consideration”.It was expected,that under themaintenance procedure some progresswould be
7、made and items“underconsideration”should be assigned toappropriate reference method.Noted3.DEGeneralFor clarification,to make the use of thestandard easier:Renumber the clauses and subclausesaccording to the numbering in the content(e.g.Introduction should be“520”and not“1”).Accept,editorial4.DKCont
8、entsEAnnex A is described as normativeChange from“(normative)”to“(informative)”Accept5.DKForewordEThe foreword is copied from the secondedition and should be changed to fit thethird edition.Reword the foreword.Accept6.DKE/GThe clause and sub-clause numberingshould be reconcidered.See 3.7.FR 2General
9、The numbering does not seem to beconsistent.To use the standard type of numbering allover the document.See 38.ITAfter careful consideration of thedocument,the Italian NC has nocomments to submit.Noted9.JPAny part ofthisdocumentEditorialThe numbering of clause,subclause,etc,shall be in accordance wit
10、h thenumbering system of IEC60364 in AnnexA of IEC60364-1,also see IEC60364-5-53 Ed.3.1:2006-06.The numbering“1,1.1,1.2,1.3,2,2.4,2.5,2.6,2.7,2.8,2.8.1,2.8.2,2.8.3,3,3.1,3.2,3.3,3.4,3.5,3.6,3.7,3Replace the numbering as follows,respectively:520,520.1,520.2,520.3,521,521.4,521.5,521.6,521.7,521.8,521
11、.8.1,521.8.2,521.8.3,522,522.1,522.2,522.3,522.4,522.5,522.6,522.7,522.8,522.9,522.10,522.11,522.12,522.13,522.14,522.15 and 523See 3 3 64/1326/CCNationalCommitteeClause/SubclauseParagraphFigure/TableType ofcomment(General/Technical/Editorial)COMMENTSProposed changeOBSERVATIONS OF THE SECRETARIATon
12、each comment submitted.8,3.9,3.10,3.11,3.12,3.13,3.14,3.15 and4”are unsuitable.10.JPP.1st lineTechnicalThis term“rating”should be clarified.Replace“rating”with:“current-carrying capacity”Accept for 523.6.3 and elsewhere ifappropriate.11.MXWe wish to inform you that the MexicanNational Committee acce
13、pt theCommittee draft without commentsNoted12.NZSupported without commentNoted13.PLThe Polish NC has no comments.Noted14.SKSK NC agrees to the documentNoted15.UKGeneralThe UK should propose that all therequirements in BS 7671 that are not in1266 be included.NotedWG2 awaits a detailed proposal16.UKGe
14、neralThe dual numbering of the CD,a 55x.x.x,etc and one decimal place numberse.g2.4,2.5 is not understood.Correct clause numbering throughout.See 317.ZAThe South African National Committeehas no comments at this stage.Noted18.DK1.2ESome references are missingAdd the following references:IEC 60364-4-
15、43(page 22)IEC 60364-5-54(page 6,note to 1.1)IEC 60364-7-715(page 22 if the Danishcomment to table 52-5 is accepted)AcceptAcceptSee comment 12519.FR 10 1.2TechnicalDelete the folowing standard referenceIEC 60614(all parts).This standard seris are replaced byIEC 61386 seriesAccept20.FR 91.2TechnicalA
16、dd the folowing standadrsIEC 61084 series:Cable trunking andcable ducting systems for electricalinstallationsIEC 61386 series:Conduits systems forcable managementIEC 61537:2001,Cable tray systemsAcceptAcceptNot accepted,no ref.In 60364-5-52 4 64/1326/CCNationalCommitteeClause/SubclauseParagraphFigure/TableType ofcomment(General/Technical/Editorial)COMMENTSProposed changeOBSERVATIONS OF THE SECRETARIATon each comment submittedand cable ladder systems for cablemanagement21.DK2.5TThe requirement is