1、暖通设计交流群7345176602.2室内空气品质与新风量37表2-40ASHRAE标准62-1989中最小新风量最大人员密度最大人员密度应用场所新风需要量应用场所新风需要量/(人/100m2)/(人/100m2)零售商店、销售店干洗衣店机、洗衣房地下室、过道305.4m3/(hm2)洗衣店1046.8m3/(h人)楼上店铺203.6m3/(hm2)干洗店3054m3/(h人)储藏室152.7m3/(h.m2)储藏、分拣3064.8m3/(h人)试衣间3.6m3/(h.m2)自助洗衣店2028.8m3/(h人)走廊203.6m3/(h.m2)自助干洗衣店28.8m3/(h人)购物与接待102.
2、7m3/(h.m2)仓库50.9m3/(hm2)汽车房、修理保养站吸烟室70100m3/(h人)封闭式停车房7.527m3/(h.m2)汽车修理房7.527m3/(hm2)特殊商店理发店2528.8m3/(h人)旅馆、汽车旅馆、旅游站、宿舍美容店2546.8m3/(h人)门厅3028.8m3/(h人)减肥沙龙2028.8m3/(h人)会议室5036m3/(h人)花店828.8m3/(h人)礼堂12028.8m3/(h人)五金、药店、布店828.8m3/(h人)宿舍、睡眠区2028.8m3/(h人)超级市场828.8m3/(h人)赌场12054m3/(h人)服装、家具店85.4m3/(h.m2)
3、卧室54m3/(h室)宠物商店2518m3/(hm2)起居间54m3/(h室)浴室64.8m3/(h室)体育与娱乐观众区15028.8m3/(h人)办公大楼娱乐室7046.8m3/(h人)办公室736m3/(h人)体操室3036m3/(h人)接待区6028.8m3/(h人)舞厅、迪斯科10046.8m3/(h人)商务中心6036m3/(h人)保龄球道(设施区)7046.8m3/(h人)会议室5036m3/(h人)溜冰场(滑冰区)9m3/(hm2)游泳池(池边区)9m3/(hm2)公共区域走廊与公共设施0.9m3/(h.m2)剧场更衣与穿衣室9m3/(hm2)票房6036m3/(h人)电梯18m
4、3/(hm2)门厅15036m3/(h人)复印与打印9m3/(hm2)观众席15028.8m3/(h人)冲印暗房9m3/(hm2)舞台、演员室7028.8m3/(h人)摄影室、照相馆1028.8m3/(h人)药房2028.8m3/(h人)交通银行金库528.8m3/(h人)候车室10028.8m3/(h人)公共厕所、小便处72m3/(h.m2)月台10028.8m3/(h人)车辆15028.8m3/(h人)教育教室5028.8m3/(h人)食品与饮料实验室、训练房3036m3/(h人)食堂7036m3/(h人)音乐室5028.8m3/(h人)咖啡店、快餐店10036m3/(h人)图书馆2028.8m3/(h人)酒吧、鸡尾酒店10054m3/(h人)厨房(烹调处)2028.8m3/(h人)