1、Designation:D732313Standard Practice forHandling,Transportation,and Storage of IG-100(Nitrogen)1This standard is issued under the fixed designation D7323;the number immediately following the designation indicates the year oforiginal adoption or,in the case of revision,the year of last revision.A num
2、ber in parentheses indicates the year of last reapproval.Asuperscript epsilon()indicates an editorial change since the last revision or reapproval.1.Scope1.1 This practice covers guidance and direction to suppliers,purchasers,and users in the handling,transportation,andstorage of IG-100(nitrogen).1.
3、2 The values stated in inch-pound units are to be regardedas standard.The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.3 This standard does not purport to address all of thesafety concerns,if any,associate
4、d with its use.It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2.Referenced Documents2.1 CGA Standards:2C-1 Methods for Pressure Testing Compressed Gas Cylin-dersC-6 Sta
5、ndards for Visual Inspection of Steel CompressedGas CylindersC-7 Guide to Preparation of Precautionary Labeling andMarking of Compressed Gas ContainersP-1 Safe Handling of Compressed Gases in Containers2.2 U.S.Government Standards,Code of Federal Regula-tions(CFR):3CFR Title 40,Part 82.106 Environme
6、ntal ProtectionAgency,Warning Statement RequirementsCFR Title 49,Part 172 U.S.Department of Transportation(DOT),Hazardous Materials Table,Special Provisions,Hazardous Materials Communications,Emergency Re-sponse Information,and Training RequirementsCFR Title 49,Part 172.101 U.S.DOT,Tables of Hazardo
7、usMaterials and Special ProvisionsCFR Title 49,Part 173 U.S.DOT Specification,Shippers-General Requirements for Shipping and PackagingCFR Title 49,Part 178 U.S.DOT Specification,Specifica-tions for PackagingCFR Title 49,Part 180 U.S.DOT,Continuing Qualificationand Maintenance of Packagings3.Terminol
8、ogy3.1 Definitions of Terms Specific to This Standard:3.1.1 containersstorage vessels for IG-100.3.1.2 cylinderscontainers of IG-100.3.1.3 IG-100(nitrogen)compound used to inert or sup-press a fire or explosion hazard.3.1.4 insulatedplaced in an isolated situation to protectand prevent the transfer
9、of damage.4.Significance and Use4.1 This practice provides requirements for the handling,transportation,and storage of IG-100 encountered in distribu-tion through both commercial and military channels.It isintended to ensure that IG-100 is handled,transported,andstored in such a way that its physica
10、l property virtues are notdegraded.Transport may be by various means,such as,but notlimited to,highway,rail and water.5.Practice5.1 To ensure safe handling,loading,unloading,storing,and transporting of material,personnel shall be trained in theCGApublications and CFR regulations as listed in Section
11、s 2.1and 2.2,respectively.5.2 Handling:5.2.1 Handling shall be in accordance with CGA P-1.5.2.1.1 Personnel who handle or store,or both,cylinders ofIG-100 shall be trained properly to recognize and identify thecharacteristics of the product and the proper methods of safelyhandling full,partially ful
12、l,and empty cylinders.5.2.2 IG-100 handling shall be in nonsmoking,heater-free,ventilated areas to preclude product accumulation.Provisionsshall be made to ensure that service areas limit IG-100concentrations to not exceed 52%(10%Sea Level Oxygenequivalency)for 30 s and 7%(19.5%Sea Level Oxygenequiv
13、alency)for 8 h.1This practice is under the jurisdiction of ASTM Committee D26 on Haloge-nated Organic Solvents and Fire Extinguishing Agents and is the direct responsi-bility of Subcommittee D26.09 on Fire Extinguishing Agents.Current edition approved March 15,2013.Published April 2013.Originallyapp
14、roved in 2007.Last previous edition approved in 2007 as D7323 07.DOI:10.1520/D7323-13.2Available from Compressed Gas Association.3Available from U.S.Government Printing Office,Superintendent ofDocuments,Washington,DC 20036.Copyright ASTM International,100 Barr Harbor Drive,PO Box C700,West Conshohoc
15、ken,PA 19428-2959.United States1 5.2.3 Cylinders shall not be overfilled.Filling density re-quirements are specified in CFR Title 49,Part 173(173.302).5.2.4 Cylinders shall be free of dirt and contamination thatwould contribute to or would cause deterioration of productduring shipment or storage.Pre
16、cautions should be taken toprevent the entry of oil,water,or any other foreign matter intocontainers.Unique coatings or preservatives applied prior toshipment to protect the containers are not considered contami-nation.5.3 Transportation:5.3.1 Transportation shall be as specified in accordance withDOT regulations of CFR Title 49.5.3.1.1 The minimum design pressure requirements shall beas indicated in CFR Title 49,Part 173.301.The pressure insidethe container at 70F(21C)shall not exceed the servi