1、IEC 61472:2013/COR1:2015 1 IEC 2015 INTERNATIONAL ELECTROTECHNICAL COMMISSION COMMISSION LECTROTECHNIQUE INTERNATIONALE _ IEC 61472 Edition 3.0 2013-04 LIVE WORKING MINIMUM APPROACH DISTANCES FOR A.C.SYSTEMS IN THE VOLTAGE RANGE 72,5 kV TO 800 kV A METHOD OF CALCULATION IEC 61472 dition 3.0 2013-04

2、TRAVAUX SOUS TENSION DISTANCES MINIMALES DAPPROCHE POUR DES RSEAUX COURANT ALTERNATIF DE TENSION COMPRISE ENTRE 72,5 kV ET 800 kV UNE MTHODE DE CALCUL C O R R I G E N D U M 1 4.3.1 General equation Replace the existing Formula(8)with the following new formula:DU=2,17(e U90/(1 080Kt)1)+F 4.3.2.5 Dama

3、ged insulator factor ki Replace the existing Formula(10)with the following new formula:DLins=2,17(e U90/(1 080Kt)1)+F 6 Calculation of minimum approach distance DA Replace the existing Formula(8)with the following new formula:DU=2,17(e U90/(1 080Kt)1)+F G.2 Damaged cap and pin insulators Replace the

4、 existing Formula(G.2)with the following new formula:DLins=2,17(e U90/(1 080Kt)1)+F 4.3.1 Equation gnrale Remplacer la Formule(8)existante par la nouvelle formule suivante:DU=2,17(e U90/(1 080Kt)1)+F 4.3.2.5 Facteur disolateur dtrior ki Remplacer la Formule(10)existante par la nouvelle formule suiva

5、nte:DLins=2,17(e U90/(1 080Kt)1)+F 6 Calcul de la distance minimale dapproche DA Remplacer la Formule(8)existante par la nouvelle formule suivante:DU=2,17(e U90/(1 080Kt)1)+F G.2 Isolateurs capot et tige dtriors Remplacer la Formule(G.2)existante par la nouvelle formule suivante:DLins=2,17(e U90/(1 080Kt)1)+F IEC 61472:2013-04/COR1:2015-10(en-fr)